Description
Description
The 9095X is a top-fill overfill prevention valve designed to prevent overfilling storage tanks by providing a positive shut-off during a pressurized fill.
For use on clean liquids only.
Standard Features
Fill adaptor and shut-off mechanism are factory-assembled for ease of field installation
Straight female threaded adaptor facilitates valve installation to a precise set point
Minimum shut-off height is 1” from the tank top
Full flow to shut-off point, cushioned closure eliminates shock
Drop tube adaptor accepts 2” drop fill tubes (Morrison 419)
Integral pressure relief
Integral anti-siphon function
305C—2000 cap included with 1100 and 2200 models
Mechanical Test Mechanism
Verify the operation of the valve by activating the test mechanism at any time during the filling process
Available on all models
Construction Details
- Direct fill adaptor: Passivated aluminum
- Remote fill adaptor: Powder coated ductile iron & stainless steel
- Shaft, linkage, and hardware: Sstainless steel
- Lower pipe nipple: E-coated steel
- Body: Passivated aluminum
- Drop tube adaptor: Passivated aluminum
Operational Criteria
Minimum 5 PSI flow requirements
Maximum operating pressure is 100 PSI
Maximum viscosity of 300 centistokes
A tight fill connection is required for the valve to operate
The estimated flow rate is 230 GPM at 10 PSI pressure drop
Code Compliance
ULC-S661-10 listed, NFPA 30, 30A, UFC, IFC, PEI/RP 200, PEI/RP 600, Florida DEP EQ-858, and California EVR models available